Ventilation
Simulation and Testing of fan for operation at 600ºC
2007

Both the fan and its supports must be designed for working under fire conditions. For road tunnels, these requirements usually imply ensuring fan normal operation at 450ºC during, at least 2 hours. But sometimes additional safety requirements have to be met. This was the case of a fan that was manufactured in 2006 for a mine in Peru. The client required ensuring proper operation at 600ºC during half an hour. To certify this, a physical test had to be carried out before installation in field. The overall design was structurally checked by simulation to ensure that this requirement was going to be fulfilled and therefore that the physical test was going to succeed.

Particularly critic was the fan motor which had to be cooled for correct operation, so a special refrigeration system was designed with the aid of simulation.

The fire test was carried out in an independent lab in Germany in February 2007. Finally, the fan was able to withstand the temperature condition (600ºC) at normal operation during more than one hour, which was an important achievement both for AST and for the technical team of the fan manufacturer.

 

  • Design and/or mechanical simulation of most of the components of the ventilation system (fan casing, supports, blades etc.)
  • Design and CFD simulation of the fan cooling system
Highlights
2024-10-14
2024 NAFEMS Iberia Conference
Universidad Politécnica de Madrid (UPM), Madrid. 14 November 2024
2024-09-10
WEDUSEA - Innovative wave energy project receives green light from EU
PRESS RELEASE - 9th September 2024
2023-11-01
NAFEMS seminar: The Challenges of New Advanced Simulation Techniques
Thursday 16 November 2023 | Madrid, Spain
2023-09-20
Actualización en el registro de PYMES INNOVADORAS
AST recibe nuevamente el sello de PYME Innovadora
2022-09-27
NRC22 Iberia
Register Today! 6 October 2022, Madrid Spain
History